60 hp AC motor soft starter, 45 kW three phase 240v, 400v, 480v, 690v.
| Model | GS2-045 (220v, 240v), GS3-045 (380v, 400v, 415v), GS4-045 (460v, 480v), GS6-045 (575v, 690v). | ||
| Capacity | 60 hp (45 kw) | ||
| Current | 90 amps at 380v/480v, 180 amps at 220v, 55 amps at 690v | ||
| Weight | 5 kgs | ||
| Dimension | 270*146*160 mm | ||
| Input | Voltage | Three-phase 220v, 400v, 480v, 660v AC | |
| Frequency | 50Hz/ 60Hz | ||
| Adaptive Motor | Squirrel-cage three-phase asynchronous motor | ||
| Starting Times | It is recommended not to exceed 20 times per hour. | ||
| 485 Communication | DB9 interface, male plug, ① is RS485+, ⑥ is RS485- | ||
| Control Mode |
| ||
| Start Mode |
| ||
| Stop Mode |
| ||
| Protective Function |
| ||
| Ambient | Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. | |
| Altitude | Below 1000M. It has to increase the soft starter rate power when the altitude is more than 1000M. | ||
| Temperature | -30 +55 oC | ||
| Humidity | 90%RH without dew condensation. | ||
| Vibration | <0.5G | ||
| Structure | Enclosure | IP 20 | |
| Cooling | Natural wind cooling. | ||
Details
Tips: The causes of soft starter SCR damage
1. When the motor starting, the overcurrent will breakdown the soft starter. It is recommended to check whether the power of soft starter matches the power of the motor and whether the motor is on-load starting.
2. The soft starter's cooling fan is damaged. It is recommended to replace the fan.
3. Start up frequently, and high temperature will damage SCR. It is recommended to control the number of times of starting.
4. The filter board is damaged, input default phase, it is recommended to replace the damaged components. There are many factors that cause this failure:
- Check whether the power incoming line and the motor incoming line are loose.
- Whether the output is connected with load, whether the load matches the motor.
- Using a multimeter to check whether the module or SCR of the soft starter is breakdown, and whether the trigger gate resistance meets the normal requirements (typically around 20-30 ohms).
- Whether the internal socket wiring is loose.